• LEAD LINED DRYWALL/GYPSUM BOARD OR PLYWOOD
  • LEAD LINING IN FLOORS
We start out by using only fire code gypsum materials for all lead-lined drywall/gypsum products. The drywall should conform to ASTM C36. Lead lining should be from 1/32″ – 1/16″ and if necessary 1/8″, although not recommended due to the heavy weight and handling. A recommended thickness of a single un-pierced sheet of lead in any chosen length is applied and bonded to the appropriate length of drywall/gypsum board. The drywall/gypsum boards are available in a minimum size of 4′ x 8′ to a maximum 4′ x 10′ x 5/8″ minimum thickness. 1/2″ thick drywall is available but not recommended.

DrywallInstall_DiagramInstall leaded side of drywall/gypsum board, lath or plywood that will be used to cover the sheet lead against wooden or metal studs ensuring that you match the joints of the sheet lead used. Material must be in a vertical position with joints running from floor to ceiling as required by standards. Drill pilot holes as necessary to prevent deformation of fastener, lead or distortion of board. A minimum lead overlap of one inch is required at all joints and corners. Extend lead overhang at least one inch into all frames or openings. Sheet lead over 1/16″ thick should have a minimum 2″ overhang. Fastened to the wooden or metal studs, using proper drywall screws of the correct length. We suggest you use a minimum of 40 screws per 48″ x 84″ sheet. Spacing the screws at a maximum of 8″ on centre at the edges and a maximum of 12″ on centre at the intermediate studs. Screw drywall screws in deeper that normal into wall covering material slightly deeper than the thickness of the lead tab/disk or buttons been used. For drywall/Gypsum board or lath you may create a dimple over the screw head with a swing of your hammer head or other round ended tool to make a 1″ diameter impression. Finish by gluing with a construction adhesive the lead buttons usually a minimum of a 7/8″ disk over each screw head. After glue has dried out fill in and feather out with wood filler or plaster compound as needed to completely cover the screws and the protection disk devices.

MarShield recommends the use of drywall screws in all situations wherever possible. If using lead headed nails (on wood studs only), then ensure that you drive them to the proper depth and cover with drywall compound.

NoteDue to the extreme weight of lead lined drywall, extra care must be taken during handling, storage and installation. Be sure to have any installed shielding tested by approved personnel.

Typical Details for Lead Lined Drywall:


LeadBlanketSpecifications

Available in 48 Inch Width

Sample Leaded Drywall Weights

  • Drywall 1/2″ thick with 1/32″ thick lead = 3.575 pounds per square foot
  • Drywall 5/8″ thick with 1/32″ thick lead = 4.75 pounds per square foot
  • Drywall 5/8″ thick with 1/16″ thick lead = 6.05 pounds per square foot
  • Drywall 5/8″ thick with 3/32″ thick lead = 8.65 pounds per square foot

Drywall 5/8″ thick with 1/8″ thick lead = 9.8 pounds per square foot

The information provided on this page should only be used as a general guideline. MarShield makes no guarantees or warranties to its accuracies. Most states or provinces have their own local by-laws, provincial, state or federal guidelines on installation & construction practices, radiation protection and proper materials to be used. Marshield assumes no liability for sheet lead installation and strongly advises that you consult with your local authorities and/or by-laws before you begin your construction project.
 
 